ESFR(Early SuppressionFast Response) FIRE SPRINKLER K242=K16.8, K363=K25.2
1
Style
Upright
Pendant
2
Model
ESFR 16.8(242) and ESFR 25.2(363)
3
Material
Bronze forging
4
Surface finish
Natural brass
5
Normal diameter (mm)
DN20 or DN25
6
Connecting thread (inch)
R3/4" or R1" NPT/BSPT
7
Response element
Fusible alloy
8
Operating Temperature
68°C/74°C/82°C/100°C
9
Response type
Fast
10
K factor
242 (16.8@ US) or 363 (25.2 @ US)
11
Working pressure
0.1 MPa - 1.2 Mpa(1 bar - 12 bar)
12
Seal material
Rubber O-ring
13
Ceiling Height
Greater than 45ft(13.7m) up to and including 48ft(14.6m) and a storage arrangement up to including 43ft(13.1m)
ESFR-363/242 early suppressionquick response sprinkler is the sprinkler with the largest flow and diameter in the world which is a major component of the automatic sprinkler system. It is mainly used to detect fire and automatically extinguish it.ESFR-363 sprinklers fast response and deliver more water to suppress fire than regular sprinklers. ESFR-363/242 sprinklersbe permitted to be used to protect general hazardous locations, warehouses storing Class I-IV items, plastic items and miscellaneous items. This system, installed at the ceiling, use large volumes of water delivering large water droplets at a high velocity to knock down the fire plume and provide enhanced protection for High Piled Storage.