Content
Fusible Alloy Pendent Sprinkler
Publish time 2024-01-25 15:25
Product information
Technical Data
TABLE
1
MODEL ESFR PENDENT
/UPRIGHT
SPRINKLER TECHNICAL DATA
Pendent Sprinkler
Upright Sprinkler
Orifice Size
3/4INCH / DN20
1INCH/DN25
Thread Size
3/4
"
pipe thread
1
"
pipe thread
Nominal K-Factor
K-14.0(K=202)
K-16.8(K=242)
K-22.4(K=320)
K-25.2(K=363)
Temperature Rating
1
65˚F (74˚C)
212˚F (100˚C)
Maximum
Service Pressure
175 psig /1.2MPa (12 bar)
Sprinkler Finish
es
:
Natural Brass
TABLE 2: AVAILABLE SPRINKLER TEMPERATURE RATING
Temperature Classification
Temp
.
Rating
Maximum Ambient Temp
.
Link Color
Ordinary
1
65˚F (74˚C)
100
˚F
(38
˚C
)
black
Intermediate
212˚F (100˚C)
150
˚F
(66
˚C
)
white